ANTSPACE HK3
Price range: $43,999 through $55,000
We added you to this product's waitlist and we'll send you an email when the product is available.
Leave WaitlistThis product is currently sold out.
No worries! Enter your email, and we'll let you know as soon as it's back in stock.
Subscription successful
You’re now subscribed to price tracking for this product. We’ll notify you if the price drops.
Standart Shipping
DHL, UPS and FedEx
6-10 Days
Free
Express Shipping
DHL , FedEx dan Global Express
3-4 Days
$149

Description
Built with efficiency and hotter climates in mind, the BITMAIN ANTSPACE HK3 (known as model designation Antbox H3 V2 internally) has a maximum capacity of 210 units Rack Space.

Bitmain’s First Liquid Cooling Antbox

Diagram of Liquid Cooling Antbox water circuit

Specifications
| Input voltage, V | 415±5% AC/60Hz/3P/N/PE |
|---|---|
| Total power consumption, kW (load shared by two power distribution cabinets) |
1047 |
| Miner power consumption W | 4900-5400 |
| Miner inlet/outlet water temperature, ℃ | 35/45 |
| Container size (length * width * height) | 6058*2438*2896 |
| Cooling tower size (length*width*height) | 5800*2240*4286 |
| Weight, T (empty weight of cooling tower/operating weight) | 6/10 |
| Weight, T (container without miner/with miner weight) | 8/12 |
| Cooling tower spray flow, m³/h | 233 |
| Heat dissipation capability kW | 1000 |
| Inlet and outlet temperature rise ΔT,° | 10 |
| Cooling tower docking interface specifications | DN125 |
| Heating docking interface specifications | DN100 |
| Cooling tower water inlet specifications | DN40 |
| Cooling tower drain specifications | DN65 |
| Heating piping pressure bearing capability kg | 10 |
| Design flow on heating side, m³/h | 85 |
| Temperature variation between inlet and outlet(heating side)ΔT | 10 |
Environmental Requirementss
| 1 | Cooling tower is required to be placed on flat ground, horizontal degree (±1 degree). |
| 2 | The ground surfaced is required to be hardened and stable, able to withstand at least 14-ton load. |
| 3 | A 10-ton crane is needed for unloading ANTSPACE and cooling tower. |
| 4 | Add-on items such as stairs, transformers, cables, bridge racks and cable distribution boxes are not included in the delivery of ANTSPACE. We team can provide design suggestions if needed. |
| 5 | Client needs to confirm the opening directon of container and it needs to face air-intake. Door on left is current design by defult. |
| 6 | Keep at least 2 meters of air in-take space around the cooling tower. |
| 7 | Altitude: ≤3000m. If the altitude is higher than 1000-meter, transformer and switch should be derated, the total power of ANTSPACE must be decreased by 1% for each elevation increment of 100 meters. |
| 8 | Operating temperature: -25°C to 40°C. Operating humidity: 10%RH to 90%RH. When the initial coolant temperature is below 20 °C, the internal circulation should be turned on to heat up the coolant to above 20 °C before starting the mining machine. |
| 9 | When the ambient temperature is below 5 ℃, the cooling tower can be switched to cold-dry mode. |
| 10 | Choose pure water or suitable antifreeze as coolant based on local climate conditions. |
| 11 | The suitable ambient temperature for ANTSPACE does not represent the suitable ambient temperature for mining machine. |